Model Number: ET70115CR24 Next Generation Time Switches
These electronic time switches provide to-the-minute programming for 7-day or full year load control. Features: 12/24 Hr clock format, 99 holiday schedules, and auto daylight savings time adjustment. 1, 2, and 4 circuit models feature 1,000+ ON/OFF events; 8 and 16 circuit models feature 4,000+ ON/OFF events. Flexible load control is enhanced by Astro, Variable Pulse, and Interval options as required for outdoor lighting control, bell ringing and after hour temporary override respectively. Non-volatile memory maintains all programmed switching times for the life of the time switch. A factory installed field replaceable lithium battery maintains accurate time keeping and calendar information for a minimum of 8 years.
Specifications
•Case
•1 and 2 circuit models: NEMA 1 – Drawn steel 7-3/4" (19.7 cm) High, 5" (12.7 cm) Wide, 3" (7.6 cm) Deep in gray finish. NEMA 3R – Drawn steel 9-3/8" (23.8 cm) high, 5-1/2" (14.0 cm) wide, 3-5/8" (9.0 cm) deep in gray finish.
•4 circuit models: NEMA 3R – Heavy duty .047" 18 gauge steel in gray finish; 12-1/2" (31.7 cm) High, 8-1/4" (21.0 cm) Wide, 4" (10.2 cm) Deep.
•8 circuit models: NEMA 3R - Heavy duty .048" steel in gray finish; 10-3/4" (27.3 cm) High, 11-1/2" (29.2 cm) Wide, 4-3/4" (12.1 cm) deep with lockable hasp.
•16 circuit models: NEMA 3R - Heavy duty .060" steel in gray finish; 20-5/8" (52.4 cm) High, 13-1/4" (33.7 cm) Wide, 5-1/8" (13.0 cm) Deep with lockable hasp.
•ON/OFF Events – 1,000+ events for 1, 2 and 4 circuit models; 4,000+ events for 8 and 16 circuit models
•Knockouts – For 1, 2 and 4 circuit models: Combination 1/2"-3/4" nominal knockouts, one on back and each side of case and two on bottom.
•Optional Enclosures – For 1, 2 and 4 circuit models: See Time Switch Cases for optional enclosures.
•Special Voltages and Cycles – Line voltage models 50 or 60 Hz; Low voltage models 60 Hz 24 Volts.
•Switch Rating – Each Pole; 20 amp resistive/general purpose, 12–277 Volts AC; 20 amp resistive/general purpose, 28 Volts DC; 20 amp ballast, 120–277 VAC; 1 HP, 120 VAC 60 Hz; 98 LRA; 22 FLA; 2 HP, 240 VAC 60 Hz; 80 LRA; 30 FLA; 5 amp tungsten, 120–240 VAC; 470 VA pilot duty, 12–240 VAC; TV-5, 120–240 VAC
•Carry-over – Non-volatile memory requires no backup. Time keeping and calendar data maintained within 0.01% accuracy for minimum of 8 years with one factory installed, field replaceable lithium coin cell.
•Wiring Terminals – #18 to #10 AWG wire
•Minimum ON/OFF Times – 1 minute
•Maximum ON/OFF Times – 6 days 23 hours 59 minutes
|